Hioki PQ3100 Power Quality Analyser

POWER QUALITY ANALYZER

PQ3100

3-Phase 4-Wire Power Quality Analyzer Compliant to IEC61000-4-30 Class S Standards and On-screen Guide to Deliver Easy Setup and Testing


Hioki portable power analyzer PQ3100 is best in class power measuring instruments for measuring single to three-phase lines with a high degree of precision and accuracy. The PQ3100 is a comprehensive but easy-to-use power quality analyzer for monitoring and recording power supply anomalies, allowing their causes to be quickly investigated, and also for assessing power supply problems such as voltage drops, flicker, harmonics, and other electrical issues. Key Features • Record data including voltage, current, power, harmonics, and flicker simultaneously along a single time axis • Measure up to 6000 A AC • Capture all power anomalies, including instantaneous outages, voltage drops, and frequency fluctuations, while simultaneously recording trend data • Quick Set: Easy-to-understand on-screen guide for measurement procedures • Bundled PQ ONE application software makes it easy to create reports • Record waveforms for up to 1 second before and 10 seconds after an anomaly occurs • Accurately measure DC currents over extended periods of time (with an AC/DC auto-zero current sensor) • Directly supply power to connected current sensors • Send measured values to HIOKI data loggers using a Bluetooth® wireless technology compatible adapter (LR8410 Link-compatible products), Ver. 2.0 and later

Basic specifications (Accuracy guaranteed for 1 year, Post-adjustment accuracy guaranteed for 1 year)

Measurement line typeSingle-phase 2-wire, Single-phase 3-wire, Three-phase 3-wire or Three-phase 4-wire plus one extra input channel CH4 for voltage/current, (all channels AC/DC measurement)
Voltage rangesVoltage measurement: 1000.0 V rms or DC, Transient measurement 2.200 kV peak
Current ranges50.000 mA AC to 5.0000 kA AC, 10.000 A DC to 2.0000 kA DC
(depends on current sensor in use)
Power ranges50.000 W to 6.0000 MW (determined automatically based on current range in use)
Basic accuracyVoltage: ±0.2% of nominal voltage, Current: ±0.1 % rdg. ±0.1 % f.s. + current sensor accuracy, Active power: DC ±0.5 % rdg. ±0.5 % f.s. + current sensor accuracy, AC ±0.2 % rdg. ±0.1 % f.s. + current sensor accuracy
Measurement items1. Transient over voltage : 200 kHz sampling
2. Frequency cycle : Calculated as one cycle
3. Voltage (1/2) RMS, Current (1/2) RMS: one cycle calculation refreshed every half cycle
4. Voltage swell, Voltage dips, Voltage interruption, RVC (Ver. up) : Voltage (1/2) RMS calculation
5. Inrush current : half-cycle calculation: Calculated as the current RMS value for current waveform data sampled every half-cycle.
6. Frequency 200 ms: Calculated as 10 or 12 cycles
7. 10-sec frequency: Calculated as the whole-cycle time during the specified 10 s period
8. Voltage waveform peak, Current waveform peak
9. Voltage, Current, Active power, Apparent power, Reactive power, Active energy, Apparent energy, Reactive energy, Energy cost, Power factor, Displacement power factor, Voltage unbalance factor, Current unbalance factor
10. Voltage crest factor, Current crest factor
11. Harmonic/ Harmonic phase angle (voltage/ current), Harmonic power: 0 th to 50 th orders
12. Harmonic voltage-current phase angle: 1 th to 50 th orders
13. Total harmonic distortion factor (voltage/ current)
14. Inter harmonic (voltage/ current): 0.5 th to 49.5 th orders
15. K Factor (multiplication factor)
16. IEC Flicker, Δ V10 Flicker
RecordMaximum recording interval: 1 year, Maximum number of recordable events: 9999 × 365 days
InterfacesSD/SDHC memory card, RS-232C (for communication/ LR8410 link), LAN (HTTP server/ FTP/ Send e-mail), USB 2.0 (for communication)
Logger connectivitySends measured values wirelessly to logger by using a Bluetooth® wireless technology serial conversion adapter. (Supported devices: Hioki LR8410 Link-compatible loggers), Ver. 2.0 and later
Display6.5-inch TFT color LCD (640 × 480 dots)
Power supplyAC adapter Z1002 (100 V to 240 V AC, 50/60 Hz, rated current 1.7 A), Battery pack Z1003 (Continuous use: 8 hr, Charging time: Max. 5 hr 30 m with AC adapter)
Dimensions and mass300 mm (11.81 in)W × 211 mm (8.31 in)H × 68 mm (2.68 in)D, 2.5 kg (88.2 oz) (including battery pack)
AccessoriesInstruction manual ×1, Measurement guide ×1, Voltage cord L1000-05 ×1 set (Red/Yellow/Blue/Gray/Black, Alligator clip ×5, Spiral tube ×5), Color clip (for identifying clamp sensor color) ×1 set, Spiral tube ×5, AC adapter Z1002 ×1, Strap ×1, USB cable (1 m 3.28 ft length) ×1, Battery pack Z1003 ×1, PQ ONE (software, CD) ×1

Options

Current input

For power or load current measurement (1 sensor necessary for single-phase measurements, and 2 or 3 sensors required for 3-phase measurements)
AC CURRENT SENSOR CT7126
60 A AC, φ 15 mm (0.59 in), 2.5 m (8.20 ft) cord length
AC CURRENT SENSOR CT7131
100 A AC, φ 15 mm (0.59 in), 2.5 m (8.20 ft) cord length
AC FLEXIBLE CURRENT SENSOR CT7040 series
• 10 Hz to 50 kHz, ±1.5% accuracy • 600A or 6000A AC rated
AC CURRENT SENSOR CT7136
600 A AC, φ 46 mm (1.81 in), 2.5 m (8.20 ft) cord length

Leak current input

*For leak current measurement (not capable of power measurement)
AC LEAKAGE CURRENT SENSOR CT7116
6 A AC, φ 40 mm (1.57 in), 2.5 m (8.20 ft) cord length

AC/DC current input

AC/DC AUTO-ZERO CURRENT SENSOR CT7731
• DC to 5 kHz, ±1.0% accuracy • Rated 100A AC/DC
AC/DC AUTO-ZERO CURRENT SENSOR CT7736
• DC to 5 kHz, ±2.0% accuracy • Rated 600A AC/DC
AC/DC AUTO-ZERO CURRENT SENSOR CT7742
• DC to 5 kHz, ±1.5% accuracy • Rated 2000A AC/DC

Hands-free options

When using with PQ3100 / PQ3198, suspend the main body on the metal surface using two Z5020 powerful type.
Z5004 hang the cords on the metal surface.
MAGNETIC STRAP Z5020
Extra strength
MAGNETIC STRAP Z5004





Cases

Waterproof Box
For outdoor installation; IP65 compliant, Contact for a quotation.

CARRYING CASE C1001
Soft type, Includes compartment for options
CARRYING CASE C1002
Hard trunk type, Includes compartment for options
CARRYING CASE C1009
Bag type, Includes compartment for options

You may send your inquiries to info@indiameters.in or call directly at 033-22350923 / 8961089611.

If you are based in Kolkata, you can directly buy from store. The address is:
Industrial Supply Syndicate, 54, Ezra Street, Kolkata - 700001